Full Function Machine Safety Tester IEC/EN60204-1 and Low Voltage Distribution and Control Devices IEC/EN61439-1-2 Measurements according to IEC/EN60204-1: Dielectric withstand voltage at industrial frequency with a test voltage of 1000 V AC Protection against indirect contact testing: Continuity of protective conductors with a test current of 200 mA Automatic power disconnection (RCD, circuit breaker, fuse) RCD disconnection (AC, A, B types) up to 1A in TT systems Magnetic-thermal protection (testing circuit breaker curves B, C, D, K) and fuses (gG, aM) in TN systems Insulation resistance measurement with a 500 V DC test voltage Residual voltage discharge V<60V in 5 sec/1 sec
Measurements according to IEC/EN61439-1-2: Clearances and creepage distances: Dielectric withstand voltage with test voltage up to 3400/5100 V AC Continuity of grounding and protective conductors ≥10A Power supply frequency Dielectric withstand voltage with test voltage up to 1800 V AC AC voltage withstand testing up to 5100 V Insulation material enclosures testing: Dielectric withstand voltage with test voltage up to 2835 V Residual voltage discharge V<60V in 5 sec/1 sec